Wuhan Huaying Electric Power Tech & Science Co., Ltd

Wuhan Huaying Electric Power Tech & Science Co., Ltd 20 YEARS experience in design and manufacture Hipot Test Set Export to 50 Countries Worldwide Professional Technical Support ISO/CE/CNAS/SGS

Manufacturer from China
Active Member
8 Years
Home / Products / Transformer Oil Testing Equipment /

Digital Automatic Transformer Oil Testing Equipment With Most Advanced Heating Mode

Contact Now
Wuhan Huaying Electric Power Tech & Science Co., Ltd
City:wuhan
Province/State:hubei
Country/Region:china
Contact Now

Digital Automatic Transformer Oil Testing Equipment With Most Advanced Heating Mode

Ask Latest Price
Video Channel
Place of Origin :Wuhan Hubei China
Brand Name :Huaying
Certification :ISO
Model Number :HYGY
MOQ :1 Set
Price :Negotiable
Packaging Details :Wooden Case
Delivery Time :7 Working Days
Payment Terms :T/T L/C
Supply Ability :200 sets per month
Product name :Insulating Oil Tan Delta Tester
Measuring Range tgδ :Without Limit
Measuring Range Cx :15PF-300PF
Measuring Range Rx :10M-20T
Dimension :450(L)×310(W)×360(H)
Weight :21Kg
more
Contact Now

Add to Cart

Find Similar Videos
View Product Description

Digital Automatic Transformer Oil Testing Equipment With Most Advanced Heating Mode

1. Product Name:

Insulating oil tan delta tester HYGY

2. Equipment Description:

HYGY Insulating oil tan delta tester is a high-precision instrument, which can be applied to measure dielectric loss angle and Volume Resistivity of insulating oil etc. It is integrated by oil cup for dielectric loss, temperature-control equipment, temperature sensor, test-bridge for dielectric loss, AC trial electrical source, standard capacitor, high resistance meter and DC high-voltage power etc. The most advanced heating mode of high frequency induction is applied to the heating part of this instrument, which has the advantage of non-contact of oil cup and heating unit, homogeneous heating, quick velocity and convenient control etc. AC-DC-AC conversion mode is applied to AC trial electrical source so that the problem how to measure correctly under the fluctuation of voltage and frequency can be avoided. Even when the electric generator is working, the instrument can operate correctly. The inner standard capacitor is SF6 three-pole inflate capacitor, whose dielectric loss and capacitance is not influenced by environmental temperature and dampness etc. In this way, the accuracy of the instrument is guaranteed conformably after a long-time application.

Convenience and maneuverability are the most remarkable advantages of this instrument.

  • First of all, digital technology and intelligent automation measurement are applied inside the instrument, multi-mode testing.

  • Secondly, big touch screen (320mm×240mm) menu interface in Chinese is equipped, with which user can be prompted each step during the operating process.

  • Thirdly, the result can be output by printer. The user can grasp operating processes masterly without technical training

3.Technical Parameters:

Condition of Use

-5℃-40℃ RH<80%

Power Source

AC 220V±10% Without Frequency Limit

AC High Voltage Output

400V-2200V ±2% Every 100V 50VA

DC High Voltage Output

00V-2200V ±2%

Temperature Control Induction Stove

Maximal Power 500W

Temperature Control Range

<100℃

Temperature Measuring Error

±0.5℃

Control Temperature Error

0.1℃

Control Temperature Time

Room Temperature 90℃ <20min


Measuring Range

tgδ Without Limit

Cx 15PF-300PF

Rx 10M-10T

Resolution

tgδ 0.001%

Cx 0.01pF

Rx 0.01

Precision

delta tgδ:±(Reading*0.5%+0.020%)

delta Cx :±(Reading*0.5%+0.5PF)

delta Rx :±Reading * 10%

Relative Dielectric Loss Constant

Εr Calculated Automatically

Volume Resistivity

ρ Calculated Automatically

Dimension

450(L)×310(W)×360(H)

Net Weight

21KG

Oil cup technical specifciations:

⑴ Distance between High Voltage terminal

and Low Voltage terminal 2mm

⑵ Capacitance of Empty Cup 60±2PF

⑶ The Highest testing voltage Industrial Frequency 2000V

⑷ Dielectric Loss of Empty Cup tgδ<1×10-4

⑸ Liquid capacity About 40ml

⑹ Electrode Material Stainless Steel

⑺ Volume 70mm(D)×120mm(H)

Inquiry Cart 0