Dielectric Loss Power Transformer Testing Kit Multi GST / UST / CVT / GST
1. Equipment Description:
HYGS automatic tangent delta tester is applied to measure the dielectric loss and capacitor value of insulation materials in high voltage power equipment. The non-power frequency voltage source is integrated in the tester to avoid power frequency interference. That make the tester has a good performance in measurement precision.
The instrument has the following characteristics:
Large LCD display
Mass storage data
Multiple test modes
CVT test step in place
do not dismantle the high-voltage lead measurement CVT
CVT reverse shield method for measuring C0
High speed sampling signal
Multi protection security
2. Technical Parameters:
1 |
Use conditions |
-15℃∽40℃ |
RH<80% |
|||
2 |
Anti-interference |
Frequency conversion |
||||
3 |
Power |
AC 220V±10% |
Allowable generator |
|||
4 |
High output |
0.5KV∽10KV |
Every 0.1kV |
|||
Precision |
2% |
|||||
Maximum current |
200mA |
|||||
Capacity |
2000VA |
|||||
5 |
Self-excited power |
AC 0V∽50V/15A |
45HZ/55HZ 47.5HZ/52.5HZ 55HZ/65HZ 57.5HZ/62.5HZ Automatic double frequency |
|||
6 |
Resolving power |
tgδ: 0.001% |
Cx: 0.001pF |
|||
7 |
Precision |
△tgδ:±(Reading*1.0%+0.040%) |
||||
△C x :±(Reading*1.0%+1.00PF) |
||||||
8 |
measuring range |
tgδ |
Unlimited |
|||
C x |
15pF < Cx < 300nF |
|||||
|
10KV |
Cx < 60 nF |
||||
|
5KV |
Cx < 150 nF |
||||
|
1KV |
Cx < 300 nF |
||||
CVT test |
Cx < 300 nF |
|||||
9 |
CVT range |
10∽10000 |
||||
accuracy |
0.1% |
|||||
Resolving power |
0.01 |
|||||
10 |
Exterior dimension |
350(L)×270(W)×270(H) |
||||
11 |
Memory size |
The 200 group supports U disk data storage |
||||
12 |
Weight |
28 Kg |